Ramcro – KNX, 2PR 0.8mm Sol BC, PVC ins,OS, PVC jkt, Eca
Brand Name: | RAMCRO |
Part Number: | R1217 |
Product Type: | Ramcro – KNX, 2PR 0.8mm Sol BC, PVC ins,OS, PVC jkt, Eca |
Specification: | Please refer to the Datasheet on the Manufacturer’s Datasheet |
Warranty: | Manufacturer Standard Warranty |
Description
Ramcro – KNX, 2PR 0.8mm Sol BC, PVC ins,OS, PVC jkt, Eca
Details:
Ramcro – KNX, 2PR 0.8mm Sol BC, PVC ins,OS, PVC jkt, Eca
KNX, 2PR 0.8mm Sol BC, PVC ins,OS, PVC jkt, Eca
Specifications:
The Ramcro cable is an alternative to the Belden cable
KNX, 2 Pair, 0.8 mm cond diameter, Bare Copper – Solid, PVC insulation, Overall Beldfoil® shielding, PVC jacket , CPR Eca
Technical Specifications
Product Overview
- Suitable Applications: KNX, EIB cable for building management
Physical Characteristics (Overall)
Conductor
- Stranding: Solid, Conductor Count: 4, Total Number of Pairs: 2
- Material: BC – Bare Copper
- Cross Section: 0.5 mm²
- Nominal Diameter: 0.8 mm
- of Conductors: 4
Insulation
- Material: PVC – Polyvinyl Chloride
- Nominal Diameter: 1.4 mm
- Diameter +/- Tolerance: 0.05 mm
- Nominal Wall Thickness: 0.3 mm
Color Chart
- Number: Quad 1
- Color: White & Red & Yellow & Black
Outer Shield
- Type: Tape
- Material: Bi-Laminate (Alum+Poly)
- Material Trade Name: Beldfoil®
- Coverage [%]: 100%
- Thickness of Foil: 9 µm
- Drainwire Material: TC – Tinned Copper
- Drainwire Diameter: 0.4 mm
Outer Jacket
- Material: PVC – Polyvinyl Chloride
- Nominal Diameter: 6.1 mm
- Diameter – Tolerance: 0.3 mm
- Nominal Wall Thickness: 1.2 mm
Construction and Dimensions
Cabling
- Description: 1 quad covered with a polyester foil
Electrical Characteristics
Conductor DCR
- Conductor: DCR 37.5 Ohm/km
Capacitance
- Capacitance Conductor to Conductor: 50 pF/m
Voltage
- Voltage Rating: [V] 300 V, Electrical Characteristics Notes: Testvoltage 4 kV, 1 min
Temperature Range
- Storage Temperature Range: -30°C to +70°C Operating
- Temperature Range: -20°C To +70°C
Mechanical Characteristics
- Bend Radius During Installation: 61 mm
- Min Setting Radius: 30 mm
Standards
- CPR Euroclass: Eca
Applicable Environmental and Other Programs
- Environmental Space: Indoor – Euroclass Eca
Flammability, LS0H, Toxicity Testing
- IEC Flammability: IEC 60332-1-2